5.3 Description of Function Codes 5.3.8 J codes (Applied functions)
5-283
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
J57
PID Control (Dancer position set point)
Related function codes: d150 PID Control (Dancer upper limit warning position)
d151 PID Control (Dancer lower limit warning position)
J57 specifies the dancer position set point in the range of -100 % to +100 % for dancer control. If J02 = 0 (keypad)
is selected, this function code is applied for the dancer position set point.
It is also possible to modify the set point (PID command) with the / keys on the keypad. If modified, the new
set point value is stored as J57 data automatically.
For the setting procedure of the set point (PID command), refer to Chapter 3 “3.3.5 Setting up PID commands from
the keypad.”
Dancer upper limit warning signal “D-UPFL” assignment (Function code E20 to E24, E27, data = 135)
Dancer lower limit warning signal “D-DNFL” assignment (Function code E20 to E24, E27, data = 136)
Dancer position limit warning signal “D-FL” assignment (Function code E20 to E24, E27, data = 137)
Dancer upper/lower limit warning output (d150, d151)
A dancer position upper limit position warning, lower limit position warning, and upper/lower limit position warning
can be output when performing dancer control. The upper/lower limit position settings are specified in the -100% to
+100% range in d150 and d151, respectively.
Setting range
Factory default
d150
PID control dancer upper limit
warning position
-100.0 to 100.0%
100.00%
d151
PID control dancer lower limit
warning position
-100.0 to 100.0%
0.00 %
Table 5.3-24 Output conditions for dancer position upper/lower limit warning signals
E20 to E24, E27
Operating condition 1
Operating condition 2
“D-UPFL”
(Setting value: 135)
This is valid when the
dancer position
enters the
intermediate position
detection range (J57
±J58) after operation
starts.
ON when dancer position > dancer upper limit warning position [d150]
OFF when dancer position ≤ dancer upper limit warning position [d150]
“D_DNLF”
(Setting value: 136)
ON when dancer position < dancer lower limit warning position [d151]
OFF when dancer position ≥ dancer lower limit warning position [d151]
“D_LF”
(Setting value: 137)
ON when “D_UPLF” = ON or D_DNLF = ON
OFF when “D_UPLF” = OFF and D_DNLF = OFF
d150上限予報位置
OFF
ONOFF
ON
OFF ON ON
ONON ONOFF
d151下限予報位置
J57中間位置
中間位置検出幅
J57±J58
上限位置予報検出出力
[135D_UPLF]
下限位置予報検出出力
[136D_DNLF]
上下限位置予報検出出力
[137D_LF]
サロ出力
t[s]
運転
Dancer roll output
Dancer upper limit
warning position
Dancer intermediate
position
Dancer lower limit
warning position
Intermediate position
detection width
Run
Upper limit position
warning detection output
Lower limit position
warning detection output
Upper/lower limit position
warning detection output