5.3 Description of Function Codes 5.3.11 U1 codes (Customizable logic operation)
5-410
Setting examples of customizable logic
Setting example 1: Use one switch to change multiple signals
If you use one switch to change the frequency setting 2/frequency setting 1 and torque limit 2/torque limit 1
simultaneously, replace an external circuit that is conventionally needed with a customizable logic reducing the
general-purpose input terminals used to a single terminal.
To configure this customizable logic, set the function codes as follows. (Timer selection) and (Timer setting) do not
need to be modified if no change is made.
Function code
Setting
value
Setting
Remarks
E01
Terminal [X1] (Function selection)
11
Select frequency command
2/1 “Hz2/Hz1”
Can be used in
parallel as
general-purpose
input terminals
U00
Customizable Logic (Mode selection)
1
Enable
U01
Customizable logic:
Step 1
(Block
selection)
10
Through output + General-
purpose timer
Mode selection
U02
(input 1)
4001
Terminal [X1] input signal “X1”
U71
Customizable logic:
Output signal 1
(Output
selection)
1
Output of step 1, “SO01”
U81
(Function
selection)
14
Select torque limiter level 2/1
“TL2/TL1”
Inverter
Customizable logic
Step 1
Hz2/Hz1