Setting example 2: Consolidating multiple output signals into one
If the general-purpose RUN signal is kept ON at restart after momentary power failure, replace an external circuit
that is conventionally needed with a customizable logic sequence to reduce the general-purpose output terminals
and external relays.
To configure this customizable logic, set the function codes as follows. (Timer selection) and (Timer setting) do not
need to be modified if no change is made.
Function code
Setting
value
Setting
Remarks
E20
Terminal [Y1] (Function selection)
111
Customizable logic output signal 1
“CL01”
U00
Customizable Logic (Mode selection)
1
Enable
U01
Customizable logic:
Step 1
(Block
selection)
30
Logical OR + general-purpose timer
Mode
selection
U02
(input 1)
0
During operation “RUN”
U03
(input 2)
6
Auto-restarting after momentary
power failure “IPF”
U71
Customizable logic
output signal 1
(Output
selection)
1
Output of step 1, “SO01”
U81
(Function
selection)
100
No function assigned “NONE”
Inverter
Customizable logic
Step 1