5.3 Description of Function Codes 5.3.11 U1 codes (Customizable logic operation)
Setting example 2: Consolidating multiple output signals into one
If the general-purpose RUN signal is kept ON at restart after momentary power failure, replace an external circuit
that is conventionally needed with a customizable logic sequence to reduce the general-purpose output terminals
and external relays.
To configure this customizable logic, set the function codes as follows. (Timer selection) and (Timer setting) do not
need to be modified if no change is made.
Terminal [Y1] (Function selection)
Customizable logic output signal 1
“CL01”
Customizable Logic (Mode selection)
Customizable logic:
Step 1
Logical OR + general-purpose timer
Auto-restarting after momentary
power failure “IPF”
Customizable logic
output signal 1
No function assigned “NONE”