6.4 If a Warning Code is Displayed
6-29
6.4 If a Warning Code is Displayed
6.4.1 Warning code list
It is possible to display a warning cause code while the inverter continues to run, and output a warning signal from
the Y terminal. To display the warning, select with function codes H81, H82, or H83. (See Chapter 5 “FUNCTION
CODES”.)
If outputting warning signals from the Y terminal, set 98 L-ALM for the function codes corresponding to E20 to E24.
Table 6.4-1 Warning code list
Mode selection
Function code
Machine life (Number of startups)
Refer to Chapter 5 “FUNCTION CODES” -
“5.3.5 H codes (High performance functions)”.
Cooling fin overheat early warning
Motor overload early warning
Machine life (Cumulative motor running hours)
6.4.2 Warning cause and check
[ 1 ] CnT Machine life (Number of startups)
(1) Inverter life (Number of
startups)
This is displayed when the number of times that the motor is started
reaches the number of times set with function code H79 (maintenance
setting startup count).
Furthermore, the current startup count can be checked at function code
H44 (startup count), and therefore the H44 data should be set to “0000”
to reset the count.
[ 2 ] iGb IGBT lifetime alarm
(1) IGBT power cycle life
The element temperature power cycle life for the main circuit
semiconductor IGBT due to frequent acceleration and deceleration
stoppages is estimated, and this is displayed before the design life is
reached.
[ 3 ] lif Lifetime alarm
It is judged that the service life of any one of the capacitors (DC link bus
capacitors or electrolytic capacitors on PCBs), the cooling fan, or the
IGBT has expired.
(Refer to “7.4.1 Judgment on service life” in Chapter 7, and check the
part service life status in the keypad maintenance information.)