2.2 Wiring
2-27
2.2.6 Control circuit terminals (common to all models)
[ 1 ] Screw specifications and recommended wire size (control circuit terminals)
The specifications for the screws used in the control circuit wiring and the wire sizes are shown below.
The control circuit terminal block is common, regardless of the inverter capacity.
The control terminal block for the conventional model MEGA (GS1) is available as an option to allow round crimp
terminals to be connected.
Refer to Chapter 11 “11.21 Control Terminal Block (G1S Compatible) OPC-G1-TB1” for details.
Table 2.2-7 Screw specifications and recommended wire sizes
Permissible
wire
size
mm
2
(AWG)
Recommended
wire size
mm
2
(AWG)
Wire
coating
removal
size
Rod
terminal *1
Terminal
block
opening
dimension
Tightening
torque
N·m
(lb-in)
0.5 to 0.6
(4.43 to 5.31)
*1: Recommended rod terminal: Phoenix Contact Refer to Table 2.2-8 below for details.
*2: Defined according to IEC/EN 60947-1.
Table 2.2-8 Recommended rod terminals
Without insulating collar
[ 2 ] Terminal layout diagram (control circuit terminals)
Fig. 2.2-12
The following terminals will have high voltage when power is ON.
Control terminals: AUX-contact ([30A], [30B], [30C], [Y5A], [Y5C])
Insulation level
Contact output – control circuit : Reinforced insulation (overvoltage category II, pollution degree 2)
Failure to observe this could result in electric shock.
Reinforced insulation
(max. 250 VAC, overvoltage category II, pollution degree2)
Screw holes for securing control terminal block board
(2 locations (left, right), M3 screws, tightening torque: 0.7 N·m)