2.2 Wiring
2-41
INSTALLATION AND WIRING
Chap 2
SW5
<Terminal [V2] function changeover switch>
The switch can be set to either analog setting voltage input or PTC/NTC thermistor input as the
terminal [V2] function. When operating this switch, also change function code H26.
Table 2.2-17
Input type
SW5
H26 data
Analog setting voltage input
(factory default)
V2 side
0
PTC/NTC thermistor input
PTC/NTC
side
1 or 2 or 3
SW6
<Terminal [FM2] voltage/current output changeover switch>
This switch changes the output type for terminal [FM2]. When operating this switch, also
change function code F32.
Table 2.2-18
Output type
SW6
F32 data
Voltage output (factory default)
VO2 side
0
Current output
IO2 side
1 (4 to 20 mA)
2 (0 to 20 mA)
SW7
(2-pole)
<Functional safety input terminal [EN1], [EN2] enable/disable changeover switch>
This switch is used to enable or disable terminals [EN1] and [EN2]. If using functional safety
input terminals [EN1] and [EN2], be sure to set this switch to the OFF side for both the left and
right poles.
Table 2.2-19
Input type
SW7
EN1
EN2
EN1/2 terminal input disable (factory default)
ON side
ON side
EN1/2 terminal input enable
OFF side
OFF side
SW8
<Terminal [C1] current/voltage input changeover switch>
The switch can be set to either analog setting current input or analog setting voltage input as
the terminal [C1] function.
Table 2.2-20
Input type
SW8
Analog setting current input (factory default)
C1 side
Analog setting voltage input
V3 side