11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-88
Dedicated T-Link interface function codes
Table 11.22-3
No.
Function code name
Setting range
*1
Setting details
y96
G1, GX1 compatibility mode
0 to 3
0: Disable (factory default)
1: Reserved (cannot be set)
2: Enable (G1 compatible)
3: Enable (GX1 compatible)
y98
Run, frequency command
source selection
0 to 3
Select from the following.
y98
Frequency
command
source
Run command
source
0
Inverter
Inverter
1
T-link
Inverter
2
Inverter
T-link
3
T-link
T-link
o27
Operation selection when T-
LINK communication error
detected
0, 4 to 9
Immediate coast to stop & er5 trip
1
Coast to stop and er5 trip after time set at o28
elapses
2
Error ignored if communication link restored
within time set at o28
Coast to stop and er5 trip if timeout occurs
3,13 to 15
Communication error ignored and current
situation maintained
(er5 does not occur)
10
Immediate forced deceleration er5 trip after
stoppage
11
Forced deceleration and er5 trip after stopping
after time set at o28 elapses
12
Error ignored if communication link restored
within time set at o28
er5 trip after forced deceleration if timeout
occurs
o28
Operation timer when T-link
communication error detected
0.0 to 60.0 sec
Timer operating time when 1, 2, 11, or 12 set for
o27
o30
T-LINK communication card
communication format selection
0
G11 standard format
2
G9 compatible format
3
Extension format
1, 4 to 255
Use prohibited
*1 Underlined values are factory default setting values.