11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-87
SELECTING PERIPHERAL EQUIPMENT
11.22.1 T-Link Communication Card (OPC-TL)
The T-LINK communication card is used to connect the FRENIC-MEGA and Fuji programmable controller MICREX
series by T-Link. Run commands and frequency commands can be set and monitored, and function code settings
necessary for operation can be changed or checked from MICREX. The T-Link extension format can also be
selected.
Applicable port
This communication card can only be installed in the A port of the three FRENIC-MEGA option connection ports (A,
B, and C ports).
[Note] Other communication cards (DeviceNet communication card, SX-bus communication card, etc.) cannot be
installed with this communication card installed. If multiple communication cards are installed, an er4 trip will occur
at FRENIC-MEGA, and it will not be possible to cancel the trip condition until there is only one communication card
installed.
T-Link specifications
Table 11.22-2
Transmission requirements
T-Link slave I/O transmission
No. of occupied
transmission words
Total of 8 words (MICREX → inverter: 4 words, inverter → MICREX: 4 words)
Number of connectable
units
FURUKAWA ELECTRIC CO., LTD. twisted pair cable CPEV-SBφ0.9 x 1 pair, or
FURUKAWA ELECTRIC CO., LTD. twisted pair cable KPEV-SB0.5 mm
2
x 1 pair
For items not contained in the above table, T-Link specifications apply.
Station No. switch (RSW1, RSW2) settings
The T-Link station No. is set with the station No. switches (rotary switches RSW1 and RSW2). The station No.
setting range is 00 to 99.
Fig. 11.22-2
* If using multiple inverters, ensure that addresses do not overlap.
* RSW1 is set to “0”, and RSW2 is set to “0” (station No. = 00) by factory default.