11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-92
Dedicated SX-bus communication card function codes
Table 11.22-5
No.
Function code name
Setting range
*1
Setting
y96
G1, GX1 compatibility mode
0 to 3
0: Disable (factory default)
1: Reserved (cannot be set)
2: Enable (G1 compatible)
3: Enable (GX1 compatible)
y98
Run, frequency command
source selection
0 to 3
Select from the following.
y98
Frequency
command
source
Run command
source
0
Inverter
Inverter
1
SX-bus
Inverter
2
Inverter
SX-bus
3
SX-bus
SX-bus
o27
Operation selection when SX-
bus communication error
detected
0, 4 to 9
Immediate coast to stop & er5 trip
1
Coast to stop and er5 trip after time set at o28
elapses
2
Error ignored if communication link restored within
time set at o28
Coast to stop and er5 trip if timeout occurs
3, 13 to 15
Communication error ignored and current situation
maintained
(er5 does not occur)
10
Immediate forced deceleration
er5 trip after stoppage
11
Forced deceleration and er5 trip after stoppage
after time set at o28 elapses
12
Error ignored if communication link restored within
time set at o28
er5 trip after forced deceleration if timeout
occurs
o28
Operation timer when SX-bus
communication error detected
0.0 to 60.0 sec
Timer operating time when 1, 2, 11, or 12 set for
o27
o30
Communication format
selection for SX-bus
communication card
0
Standard format
1 to 255
Use prohibited
*1 Underlined values are factory default setting values.