11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-91
SELECTING PERIPHERAL EQUIPMENT
Chap 11
11.22.2 SX-bus Communication Card (OPC-SX)
The SX-bus communication card is used to connect the FRENIC-MEGA and Fuji programmable controller MICREX-
SX series by SX-bus. Automatic operation and monitoring can be performed, and function code settings necessary
for operation can be changed or checked with MICREX-SX programs.
Applicable port
This communication card can only be installed in the A port of the three FRENIC-MEGA option card connection
ports (A, B, and C ports).
[Note] This communication card uses certain B port functions, and therefore only a relay output card can be installed
in the B port.
[Note] When this communication card is installed, it cannot be used in combination with other communication cards
(DeviceNet communication card, PROFIBUS DP card, etc.) If these communication cards are mistakenly installed
at the same time, communication error alarm er4 will occur.
Hardware specifications
Table 11.22-4
Item
Specification
Name
SX-bus communication card
Transmission requirements
SX-bus slave, I/O transmission
Baud rate
25 Mbps
No. of occupied transmission
words
Standard format (16 words: 8 words + 8 words)
Terminal/bus cable
Dedicated IN, OUT/SX bus cable
* NP1C-P3 (0.3 m) to NP1C-25 (25 m)
Station No. switch RSW1, RSW2
(rotary switches)
The desired station No. can be assigned from 1 to 238 for the station No.
(address) setting.
Status indicator LED (RUN, ERR)
The local station (running, error) is indicated with an LED.