11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-94
11.22.3 PROFIBUS-DP Communication Card (OPC-PDP2)
By installing the PROFIBUS-DP communication card in FRENIC-MEGA and connecting to the
PROFIBUS-DP master device, run commands, frequency commands, and the operating status can be
monitored, and all FRENIC-MEGA function codes can be changed or referenced.
The features of this communication card are shown below.
- PROFIBUS version: DP-V0 compatible
- Baud rate: 9,600 bps to 12 Mbps
- Compatible profile: PROFIDrive V2
- Reading/writing to all FRENIC-MEGA function codes possible
Applicable port
This communication card can only be installed in the A port of the three FRENIC-MEGA option
connection ports (A, B, and C ports).
[Note] Other communication cards (DeviceNet communication card, SX-bus communication card, etc.)
cannot be installed with this communication card installed. If multiple communication cards are installed,
an er4 trip will occur at FRENIC-MEGA, and it will not be possible to cancel the trip condition until
there is only one communication card installed.
PROFIBUS-DP specifications
Table 11.22-6
Item
Specification
Remarks
Transmission
Line
RS-485 (insulated)
Connection
length
See table below.
Baud rate
9.6, 19.2, 45.45, 93.75, 187.5, 500 kbit/s
1.5, 3, 6, 12 Mbit/s (automatic detection)
Selected at master side
Transmission
protocol
PROFIBUS-DP (DP-V0)
IEC 61158, 61784
Connector
6-pole terminal block
PHOENIX CONTACT
Control
Controller
SPC3 (Siemens)
Transmission
buffer
1472 bytes (SPC3 built-in memory)
Address
Setting with rotary switch (0 to 99) or setting with
inverter function code o31 (0 to 125)
o31 is valid when the
rotary switch is set to 0.
Diagnostic function
Disconnection detection
Based on OFFL LED
Configuration error detection
Based on ERR LED
The maximum transmission distance per segment when using a PROFIBUS-DP cable is as follows.
Table 11.22-7
Communication
speed (bit/s)
Max. length per segment (m)
9.6k
1200
19.2k
1200
45.45k
1200
93.75k
1000
187.5k
1000
500k
400
1.5M
200
3M
100
6M
100
12M
100