11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-95
SELECTING PERIPHERAL EQUIPMENT
Chap 11
Function code settings
To specify run commands and frequency commands from PROFIBUS, it is necessary to set inverter function codes.
A list is shown in Table 11.22-8.
Table 11.22-8 Function code settings required to enable run and frequency commands from PROFIBUS
Function
code
Description
Factory
default
Setting change value
Remarks
y96
G1, GX1 compatibility
mode
0
0/2/3
0: Disable (factory default)
1: Reserved (cannot be set)
2: Enable (G1 compatible)
3: Enable (GX1 compatible)
y98
Run, frequency
commands from
PROFIBUS
0
3
Select from the following.
y98
Frequency
command
source
Run
command
source
0
Inverter
Inverter
1
PROFIBUS
Inverter
2
Inverter
PROFIBUS
3
PROFIBUS
PROFIBUS
y99
Run, frequency
command from rotor
0
0
Unnecessary to change from factory
default
From
E01
Terminal [X□] function
selection
(□: terminal number)
-
Set to other than
24, 1024 (other
than “LE”
selection).
(Applies to all
terminal X function
codes.)
Even when “LE” is selected, the y98
setting will be valid if the terminal is
turned ON.
When “LE” is set to OFF, the y98 setting
will be invalid, and both run and
frequency commands will be specified
from the inverter.
Other related function codes are shown in the following table.
Table 11.22-9 Related inverter function codes
Function
code
Description
Factory
default
Setting range
Remarks
o27
Operation selection
when PROFIBUS
communication error
detected
0
0 to 15
o28
Operation timer when
PROFIBUS
communication error
detected
0.0s
0.0s to 60.0s
o30
PPO TYPE
0
0 to 255
Refer to the communication card
instruction manual.
o31
PROFIBUS station No.
selection
0
0 to 125
Station Nos. that are valid when the
rotary switch on the PCB is set to “00”
o40 to
o47
Write function code
assignment 1 to 8
0000
0x0000 to 0xFFFF
Sets function code for data mapped I/O
writing.
Same as PNU915
o48 to
o55
Read function code
assignment 1 to 8
0000
0x0000 to 0xFFFF
Sets function code for data mapped I/O
reading.
Same as PNU916

Table of Contents