11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-105
SELECTING PERIPHERAL EQUIPMENT
Chap 11
Dedicated CC-Link function codes
Table 11.22-22
No.
Function code name
Setting range
*1
Setting
y96
G1, GX1 compatibility mode
0/2/3
0: Disable (factory default)
1: Reserved (cannot be set)
2: Enable (G1 compatible)
3: Enable (GX1 compatible)
y98
Run, frequency command
source selection
0 to 3
Select from the following.
Frequency
command
source
Run
command
source
0
Inverter
Inverter
1
CC-Link
Inverter
2
Inverter
CC-Link
3
CC-Link
CC-Link
o27
Operation selection when CC-
Link communication error
detected
0, 4 to 9
Immediate coast to stop & er5 trip
1
Coast to stop and er5 after time set at o28
elapses
2
Error ignored if communication link restored within
time set at o28
Coast to stop and er5 if timeout occurs
3,13 to 15
Communication error ignored and current situation
maintained
(er5 does not occur)
10
Immediate forced deceleration
er5 after stoppage
11
Forced deceleration and er5 trip after stoppage
after time set at o28 elapses
12
Error ignored if communication link restored within
time set at o28
er5 after forced deceleration if timeout occurs
o28
Timer time setting when
communication error detected
0.0 to 60.0 sec
Timer operating time when 1, 2, 11, or 12 set for
o27
o30
CC-Link extension setting
(multiple setting)
5 to 255
Disable
0, 1
1 station occupied (CC-Link version 1.10)
2
1 station occupied, 2x setting (CC-Link Ver.2.00)
3
1 station occupied, 4x setting (CC-Link Ver.2.00)
4
1 station occupied, 8x setting (CC-Link Ver.2.00)
o31
Station No. setting *2
0, 1 to 64
Station No. setting (slave: 1 to 64)
L.ERR lights up if other value set.
o32
Baud rate setting *2
0 to 4
0: 156kbps, 1: 625kbps, 2: 2.5Mbps, 3: 5Mbps, 4:
10 Mbps
L.ERR lights up if other value set.
*1 Underlined values are factory default setting values.
*2 By changing the station No. or baud rate settings while the inverter power is ON, L.ERR blinks, and communication is stopped.
Setting values are reflected by resetting “RST” from the terminal block, or the next time the power is turned ON.