11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-104
11.22.6 CC-Link Communication Card (OPC-CCL)
CC-Link (Control & Communication Link) is an FA open field network system.
Installing the CC-Link communication in the FRENIC-MEGA and connecting to the CC-Link master unit with a
dedicated cable supports a transmission speed of 156 kbps to 10 Mbps and total length of 100 to 1,200 m, allowing
it to be used in a wide range of systems requiring high-speed or long-distance transmission, enabling a flexible
system configuration.
Applicable port
This communication card can only be installed in the A port of the three FRENIC-MEGA option connection ports (A,
B, and C ports).
[Note] Other communication cards (DeviceNet communication card, SX-bus communication card, etc.) cannot be
installed with this communication card installed. If multiple communication cards are installed, an er4 trip will occur
at FRENIC-MEGA, and it will not be possible to cancel the trip condition until there is only one communication card
installed.
CC-Link specifications
Table 11.22-21
Mitsubishi Electric PLC, etc. (CC-Link master)
CC-Link version 1.10 and 2.0
(Broadcast polling system)
Number of connected inverters
Max. 42 units (one station occupied/unit)
Number of stations occupied
CC-Link version 1.10: 1 station occupied
CC-Link version 2.0: 1 station occupied (Selectable from among 2x, 4x
and 8x settings)
10 Mbps/5 Mbps/2.5 Mbps/625 Kbps/156 Kbps
Total max. cable length
(when using dedicated CC-Link
cable)
500 VDC (photocoupler insulation)
For items not contained in the above table, the CC-Link specifications apply.