0: Immediate Er5 trip when communication error occurs.
1: Immediate Er5 trip after running for time specified with
timer after communication error occurs.
2: Immediate Er5 trip if communication error occurs, and
communication does not recover after retry while running
for time specified with timer
3: Motor continues to run without Er5 trip even if
communication error occurs. Motor runs in accordance
with communication command after communication
recovers.
4 to 9: Same as o27 = 0
10: Er5 trip following deceleration stop due to
communication error.
11: Er5 trip following deceleration stop after running for time
specified with timer after communication error occurs
12: Deceleration stop if communication error occurs, and
communication does not recover after retry while running
for time specified with timer. Motor continues to run in
accordance with communication command if
communication recovers.
13 to 15: Same as o27 = 3
Example: Set as follows if 192.168.11.1 is set.
o201 = 192
o202 = 168
o203 = 11
o204 = 1 (if o213 = 1, the rotary switch setting is referenced)