11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-107
SELECTING PERIPHERAL EQUIPMENT
Chap 11
Function
code
Description
Factory
default
Setting
y98
Run, frequency command
source selection
0
Select from the following.
y98
Frequency
command source
Run command
source
0
Inverter
Inverter
1
Ethernet
Inverter
2
Inverter
Ethernet
3
Ethernet
Ethernet
o27
Transmission error
(Operation selection)
0
0: Immediate Er5 trip when communication error occurs.
1: Immediate Er5 trip after running for time specified with
timer after communication error occurs.
2: Immediate Er5 trip if communication error occurs, and
communication does not recover after retry while running
for time specified with timer
3: Motor continues to run without Er5 trip even if
communication error occurs. Motor runs in accordance
with communication command after communication
recovers.
4 to 9: Same as o27 = 0
10: Er5 trip following deceleration stop due to
communication error.
11: Er5 trip following deceleration stop after running for time
specified with timer after communication error occurs
12: Deceleration stop if communication error occurs, and
communication does not recover after retry while running
for time specified with timer. Motor continues to run in
accordance with communication command if
communication recovers.
13 to 15: Same as o27 = 3
o28
Transmission error (Timer time)
0.0
0.060.0s
o201
IP address setting 1
Example: Set as follows if 192.168.11.1 is set.
o201 = 192
o202 = 168
o203 = 11
o204 = 1 (if o213 = 1, the rotary switch setting is referenced)
o202
IP address setting 2
o203
IP address setting 3
o204
IP address setting 4
o205
Subnet mask setting 1
Example: Set as follows if 255.255.255.0 is set.
o205 = 255
o206 = 255
o207 = 255
o208 = 0
o206
Subnet mask setting 2
o207
Subnet mask setting 3
o208
Subnet mask setting 4
o209
Default gateway setting 1
Example: Set as follows if 192.168.11.1 is set.
o205 = 192
o206 = 168
o207 = 11
o208 = 1
o210
Default gateway setting 2
o211
Default gateway setting 3
o212
Default gateway setting 4
o213
IP address setting mode
0: Fixed
1: Hard switch
2: DHCP (other than PROFINE)
3: DCP (for PROFINET)
If 0, set o201 to o212.
If 1, set IP address
as o201.o202.o203.n.
o214
Protocol setting
0: None (invalid)
1: PROFINET-RT
2: EtherNet/IP
o215
KEEP-ALIVE startup time
10 to 720 s