11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-108
Write function code
assignment 1 to 32
(max. 32 words)
Set function code for writing output from master to inverter.
(Group number) × 100
H
+ 2 lower order digits of function
code (see inverter function code settings)
Example: Function code E01 = 0501
H
(hexadecimal
number)
Read function code
assignment 1 to 32
(max. 32 words)
Set function code for reading input from inverter to master.
(Group number) × 100
H
+ 2 lower order digits of function
code (see inverter function code settings)
Example: Function code E01 = 0501
H
(hexadecimal
number)
Inverter function code settings
If accessing inverter function codes, specify the function code type (Table 11.22-24) and number with a 4 digit
hexadecimal number as follows.
However, these are ignored if the inverter has no function codes.
機能コード番号(16進表記)
機能コード種別(付録表1.1による)
Table 11.22-24 Function code type
Motor 2/speed control 2 parameter
Specific purpose function
Customizable logic function
Motor 4/speed control 4 parameter
Customizable logic function
Motor 3/speed control 3 parameter
Example: In the case of F26
26 → 1A (hexadecimal notation)
Based on function code type (Table 11.22-24)
Function code number (hexadecimal notation)