11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-109
SELECTING PERIPHERAL EQUIPMENT
Chap 11
11.22.8 Digital Input Interface Card (OPC-DI)
The digital input interface card is equipped with a 16-point digital input terminal (SINK/SOURCE method switching
possible), and by installing the card in FRENIC-MEGA, the frequency can be set, and general-purpose input
terminals can be extended with a binary code (8, 12, 15, 16 bits) or BCD code (4 digits).
Applicable ports
This interface card can be installed in one of the three FRENIC-MEGA option connection ports (A, B, and C ports).
Electrical specifications
Table 11.22-25
Terminal
symbol
Item
Specification
Min.
Max.
[I1] to [I16]
Operating
voltage
(SINK)
ON level
0 V
2 V
OFF level
22 V
27 V
Operating
voltage
(SOURCE)
ON level
22 V
27 V
OFF level
0 V
2 V
Operating current when ON
(when input voltage 0 V)
2.5 mA
5 mA
Permissible leakage current
when OFF
-
0.5 mA
Terminal function
Table 11.22-26
Terminal
symbol
Terminal name
Function
[I1] to [I16]
Digital input 1 to 16
(1) The frequency can be set using the frequency setting
methods set with function codes o19 and o20.
Refer to “Function code settings” on the following page
for details.
(2) By setting function code o101 to o116, these terminal
signals can be used as general-purpose input signals in
the same way as terminal [X1] to [X9].
(3) The SINK/SOURCE method can be switched using SW1.
[M1]
External power supply input
This is a power supply input terminal used for an external
power supply (+22 to +27 VDC).
[CM]
Digital common
This is a common terminal for digital input signals.
Same electric potential as inverter unit terminal [CM]