11.22 Built-in Option Card Types and Ports in Which They Can be Installed 
 
11-110 
Connection example 
Table 11.22-27 
 
*  The  maximum  permissible  MEGA  unit  [PLC] 
terminal current is 100 mA 
 
 
Function code settings 
1. If setting the frequency 
To enable frequency setting input  from this  interface card, it  is necessary to set “11”  (digital input  interface) for 
function code F01 (frequency setting 1) or C30 (frequency setting 2). Furthermore, the frequency setting polarity 
and input mode are set with function code o19 (DI polarity selection) and o20 (DI mode selection). 
The data for each bit is “0” when terminal input is OFF, and “1” when terminal input is ON. 
Table 11.22-28 
Terminal function and description of setting content 
8-bit binary 
frequency setting 
Set resolution = Maximum output frequency x (1/255) 
12-bit binary 
frequency setting 
Set resolution = Maximum output frequency x (1/4095) 
15-bit binary 
frequency setting 
Set resolution = Maximum output frequency x (1/32767) 
16-bit binary 
frequency setting 
Set resolution = Maximum output frequency x (1/65535) 
BCD, 4 digits 
Frequency setting 
(0 to 99.99 Hz) 
The frequency can be set in the 0 to 99.99 Hz (set resolution = 
0.01 Hz) range. 
If a value equal to or higher than the maximum output 
frequency is entered, the value is restricted to the maximum 
output frequency.