11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-111
SELECTING PERIPHERAL EQUIPMENT
Terminal function and description of setting content
BCD, 4 digits
Frequency setting
(0 to 599.0 Hz)
The frequency can be set in the 0 to 599.0 Hz (set resolution =
0.1 Hz) range.
If a value equal to or higher than the maximum output
frequency is entered, the value is restricted to the maximum
output frequency.
8-bit binary
frequency setting
Frequency setting range: - (Maximum output frequency) to +
(maximum output frequency)
-128 to +127
Set resolution = Maximum output frequency x (1/127)
12-bit binary
frequency setting
Frequency setting range: - (Maximum output frequency) to +
(maximum output frequency)
-2048 to +2047
Set resolution = Maximum output frequency x (1/2047)
15-bit binary
frequency setting
Frequency setting range: - (Maximum output frequency) to +
(maximum output frequency)
-16384 to +16383
Set resolution = Maximum output frequency x (1/16383)
16-bit binary
frequency setting
Frequency setting range: - (Maximum output frequency) to +
(maximum output frequency)
-32768 to +32767
Set resolution = Maximum output frequency x (1/32767)
(Note) When o20 = 4 or 5 (BCD code), operation is performed “without polarity”.
2. If using as a general-purpose digital input
Terminals can be used as general-purpose input terminals in the same way as terminal [X1] to [X9].
90: General-purpose digital input
Terminal [I1]
(Function selection)
Same content as function codes E01 to E09
Refer to Chapter 5 “FUNCTION CODES".
Terminal [I2]
(Function selection)
Terminal [I16]
(Function selection)