11.22 Built-in Option Card Types and Ports in Which They Can be Installed
11-121
SELECTING PERIPHERAL EQUIPMENT
Chap 11
11.22.11 Relay Output Interface Card (OPC-RY)
The relay output interface card is a general-purpose output signal relay output (1C contact) card. It is equipped with
two relay outputs, and four relay outputs are possible by installing two of these interface cards.
The signals output to each relay output are set with function codes E20 to E23. By selecting active OFF with a
function code, relays can be set to a non-excitation state when active, allowing the card to be used for fail safe
applications.
By selecting function code o22 = 1, a different output setting to terminal [Y1] to [Y4] can be specified.
Applicable ports
FRENIC-MEGA is equipped with three option connection ports. Please note that restrictions apply to each
connection port.
Table 11.22-38
Port
Output signal
Output signal assignment
Remarks
When function code o22 = 0 (factory default)
When function code o22 = 1
A port
Relay output 1
Relay output 2
Function code E20 (linked to terminal Y1)
Function code E21 (linked to terminal Y2)
Function code o23 (operates independently)
Function code o24 (operates independently)
B port
Relay output 1
Relay output 2
Function code E22 (linked to terminal Y3)
Function code E23 (linked to terminal Y4)
Function code o25 (operates independently)
Function code o26 (operates independently)
C port
Connection
not possible
Terminal function
Table 11.22-39
Terminal
symbol
Terminal name
Function description
[1A]
[1B]
[1C]
Relay output 1
Terminal [Y1] (A port)/[Y3] (B port) signals are output with relay contacts.
Signals are selected with function codes o23 / o25, output with relay
contacts.
[2A]
[2B]
[2C]
Relay output 2
Terminal [Y2] (A port)/[Y4] (B port) signals are output with relay contacts.
Signals are selected with function codes o24 / o26, output with relay
contacts.
Electrical specifications
Table 11.22-40
Item
Specification
Contact capacity
250 VAC, 0.3 A COSΦ = 0.3 or, 48 VDC, 0.5 A (with resistive load)
Contact life
expectancy
250 VAC, 0.3 A: 200,000 times (if turned ON, OFF in 1 second intervals)
48 VDC, 0.5 A: 200,000 times (if turned ON, OFF in 1 second intervals)
Note) Where frequent ON/OFF switching is anticipated (for example, when selecting
signals during inverter output limiting to perform aggressive current limiting), use
terminal [Y1] to [Y4] (transistor output).
Applicable safety
standards
EN61800-5-1:2007Over Voltage Category II (reinforced insulation) 250 VAC