3.3 Running Mode
3-6
Table 3.3-1 Monitor items (cont.)
Monitor item
Monitor
example
LED indication
Unit
Meaning of displayed value
Data for E43
Motor output *3
9.85
Hz A kW
kW
Motor output (kW)
16
Load factor *4
50;
Hz A kW
%
Load factor of the motor in % as the rated
output being at 100%
15
PID output *5, *6
10.00.
Hz A kW
-
PID command/feedback amount converted
to a physical quantity of the object to be
controlled (e.g. temperature)
Refer to function codes J106 and J107 for
details.
10
PID feedback value*5,
*7
9.00.
Hz A kW
-
12
PID deviation*5, *7
1.00.
Hz A kW
-
PID command value and PID feedback
value deviation converted into physical
quantities of the object to be controlled
29
PID output *5, *6
100.0.
Hz A kW
%
PID output in % as the maximum
frequency (F03) being at 100%
14
Timer *10
50
Hz A kW
s
Remaining time for timer operation
13
Analog input monitor *8
82.00
Hz A kW
-
An analog input to the inverter in a format
suitable for a desired scale.
Refer to the following function codes.
Terminal [12]: C59, C60
Terminal [C1] (C1 function): C65, C66
Terminal [C1] (V2 function): C71, C72
17
Command position*11
765
4321.
Hz A kW
-
Alternate display of 4 higher order digits
(with sign) and 4 lower order digits
21
Positioning deviation*11
765
4321.
Hz A kW
-
Alternate display of 4 higher order digits
(with sign) and 4 lower order digits
22
Position control start
position*11
765
4321.
Hz A kW
-
Alternate display of 4 higher order digits
(with sign) and 4 lower order digits (with
sign) for position when run command ON
or when POS-SET enabled with user value
27
Stop target position*11
765
4321.
Hz A kW
-
Alternate display of 4 higher order digits
(with sign) and 4 lower order digits (with
sign) for stop target position with user
value
28
Torque current *9
48
Hz A kW
%
Torque current command value or
calculated torque current
23
Magnetic flux command
*9
50
Hz A kW
%
Magnetic flux command value
24
Input watt-hour
100.0
Hz A kW
kWh
Input watt-hour (kWh)
100
25
Winding diameter*12
54321
Hz A kW
mm
Winding diameter calculation result display
for constant surface speed control
26
Torque bias
25
Hz
A
kW
%
Torque bias value display
30
Estimated inertia
acceleration/
deceleration time
conversion value
(supported soon)
1.234
Hz
A
kW
s
Display of estimated inertia result in logic
acceleration/deceleration time
See function code P24.
31
Customizable logic
output*13
82.00
Hz
A
kW
-
Display of output content for specific
customizable logic step
See function codes U98, U99.
32
ON, OFF
*1 Calculated torque 100% is equal to the motor rated torque. For the calculation formula of the motor rated
torque, refer to E.2 “Calculated formula” (1) in Appendix E “Conversion from SI Units.”
*2 If displaying the output voltage, V is displayed as the last digit on the LED monitor to denote the unit for V
(volts).
*3 When the LED monitor displays the motor output, the unit LED indicator “kW” blinks.
*4 When the LED monitor displays the load factor, the 7-segment letter ; in the lowest digit stands for “%”.
*5 These PID related items appear only under the PID control specified by function code J01 (= 1, 2 or 3).