Appendix G Conformity with Standards
Appendix-52
[ 3 ] Inverter output status when STO is activated
When the terminal [EN1] and [EN2] are turned OFF, the inverter enters the STO state.
Fig. G.4-2 shows the inverter output status when terminal [EN1] and [EN2] are turned OFF while the inverter is
stopped.
The inverter ready status will be complete when the terminal [EN1] and [EN2] inputs turn ON.
Terminal[EN1][EN2]
Run
RUN command
Inverter output
ON
OFF
Ready to RUN
Running
Stop
STO
Stop
STO
OFF
Ready to RUN
Fig. G.4-2 Inverter output status when terminal [EN1], [EN2] is turned OFF while the inverter is stopped
Fig. G.4-3 shows the timing chart when terminal [EN1] and [EN2] are turned OFF while the inverter is running. Input
to terminal [EN1] and [EN2] turns OFF, the inverter enters the STO condition, and the motor coasts to a stop.
Terminal[EN1][EN2]
Run
RUN command
Inverter output
ON OFF
Running
STO
Fig. G.4-3 Inverter output status when terminal [EN1], [EN2] is turned OFF during inverter operation