Appendix G Conformity with Standards
Appendix-54
[ 5 ] Precautions for releasing STO
If the terminal [EN1] and [EN2] are turned OFF during inverter operation, the inverter forcibly coasts to a stop.
After that, if [EN1] and [EN2] are turned ON with the operation command being input, the inverter restarts the output.
Be careful when resetting the safety components. (Fig. G.4-5)
Terminal[EN1][EN2]
RUN command
Inverter output
ON OFF
Running STO
ON
Ready to RUN
OFF
ON
Running
Figure G.4-5 When STO is released