Chapter 13 Fan Unit Replacement 13-5
13.3 Mounting a Fan Unit
Caution – Do not forcibly mount a fan unit in a slot. Forcibly pushing a fan unit in
a slot may damage the fan unit or the server.
1. Adjust the position of the fan unit so that its latch is on the right when you are
facing the front of the server.
2. Insert the fan unit in the slot.
3. Complete the replacefru command which has been executed in the XSCF
command prompt. For details, see Section 4.4.1, “FRU Removal and
Replacement (Power supply unit/Fan unit)” on page 4-8.
13.4 Reassembling the Server
1. Attach the fan cover.
For details, see Section 5.4.2, “Attaching the Fan Cover” on page 5-8.
2. If the equipment rack is supplied with a Quake-Resistant Options Kit or
stabilizer, return to its original position.
For details, see Section 5.1.2, “Sliding the Server into the Equipment Rack” on
page 5-3.
3. From the XSCF Shell prompt, use the showhardconf command to verify that
the new fan unit has been installed.
For details, see Section 4.4.2, “Verifying the Hardware Operation (Power supply
unit/Fan unit)” on page 4-10.
XSCF> showhardconf