94 Power+ Technical Guide
The following steps only apply to systems manufactured in years 2004 – 2005.
In some older systems (manufactured in 2004 – 2005), replacement of the EPROM can cause
two alarm conditions: the USER1 and the USER2 alarms. (These alarms were not implemented
in those systems.) In the event that these alarms are active after EPROM replacement, please
perform the following actions to disable the USER1 and USER2 alarms (alarms #17 and #18).
2.
Disable alarms
2.1 From the main screen, press "ENT".
2.2 Select “7> SETUP”.
2.3 For the password press left arrow button 8 times and then “ENT”.
2.4 Select “8> Service”.
2.5 Select “5> Configure”.
2.6 Select “5> Dry, Alarms”.
2.7 Select “7> Enable/Disable Alarms”.
2.8 Use the "right" arrow to navigate to alarm number 4, then press the "down" arrow. The black
circle changes to a dash, indicating that the alarm has been disabled. If required, repeat this step
for alarms 17 and 18 (USER1 and USER2).
2.9 Press “ENT” twice to save the settings and then "ESC" twice to leave setup.
3. Enable "Current Sharing Reset" option
3.1 From the main screen, press "ENT".
3.2 Select "7>Setup".
3.3 Select "8>Service".
3.4 Select "4>En/Dis shar".
3.5 Select option number 2-"RST CURRSHAR ENABLD".
3.6 Press "ENT".
3.7 Press "ESC" to leave setup.