Gamatronic Electronic Industries Ltd.
Power+ Technical Guide 63
Table 5-3
: Log Messages "description" field
Alarm
#
Message Explanation
01 UPSMAJ More than 1 UPS Module is sending an alarm or fault warning.
02 UPSMIN Single UPS Module is sending an alarm or fault warning.
03 ------ N.A.
04 ------ N.A.
05 LOADBP
Load is now running on bypass. "Data" field holds the STSW transfer
code – see Table 5-4 for interpretation of the STSW transfer code.
06 VIBRA_
Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to avoid
loading the log filling up.
07 OVTEMP Excess temperature.
08 OUTFLT No ac output to load.
09 BAT-HI Excessive battery voltage.
10 ------ N.A.
11 BATEND End of battery backup. Battery is discharged to shutdown limit.
12 BATLOW Low battery voltage.
13 STSWRN Static Switch Warning or alarm.
14 E.P.O. Emergency Power Off is active.
15 EQ-HST
Battery is currently charging in equalizing mode, dc voltage is temporarily
increased.
16 BATFLT Batteries failed last test.
17 USER-1 User 1 input open.
18 USER-2 User 2 input open
19 USER-3 User 3 input open.
20 AC-BRN Input ac supply brown-out.
21 ACIN_H Ac input excessive.
22 ACFAIL Ac input failure.
23 STSWCM Static Switch does not respond.
24 SLFFLT Last controller self-test failed.
25 BAT-CB Battery circuit breaker open.
26 CURSHR
Current Sharing fault, load current is not equally divided between
modules.
27 UPSOUT Fault (no current) in 1 or more output stage.
28 UPSHDN UPS shutdown by EPO, Battery Discharge, ON/OFF pressed.
29 OVLOAD Load current is high.
30 UPS-CM
One or more UPS’s not responding.
31 STRTUP Startup time-stamp.
32 ------ N.A.