44 Power+ Technical Guide
3.9.6.2 Q: WHEN I LOOK AT THE LIST OF THE ALARMS, I CAN SEE SOME ALARMS WHICH
ARE ALWAYS ON
. WHY IS THAT?
A. There is a number of alarms that might be on. One of them is the STRTUP alarm, which stands for
the startup time stamp. This alarm only means that the unit is on, and it will not raise an alarm signal.
Other alarms can be the user alarm 1-4, which are the input dry contacts. If they are not in use, you
can disable them through the controller menus.
3.9.6.3 Q: WHAT WILL HAPPEN IF THE EQUALIZING MODE WAS ACTIVATED IN THE UNIT?
A. The equalizing mode should always be set to DISABLED, this feature is not available. If you had it on
in your system, please note that it could simulate a failure condition and a shutdown to the computers.
On all the units today this feature is absent. Please contact your Gamatronic representative to upgrade
your controller software version.
3.9.6.4 Q: THE UNIT ALWAYS SHOWS BATTERY TEST FAULT ALARM. THE BATTERIES
ARE
OK. WHAT IS WRONG?
A. On some older systems the controller might show false battery alarms. This was corrected, so in case
that you have this problem and positively sure that the batteries are alright, please contact your
Gamatronic representative to upgrade your controller software version. After you perform this action, the
unit will still show battery test fault. Please perform manual battery test to restore normal operation.