Chapter 6 Parameter • 106 ARTDrive V2 series - Instruction Manual
generated.
A13.14 Drv OL accum % [%] R 0.00 0.00/0.00 PV V-F-S Full 1540
Drive Unit I2t overload accumulator. When 100% is reached Drv overload alarm is
generated and output inverter current is reduced to drive continuous current.
A13.15 Std enc pos [cnt] R 0.00 0.00/0.00 PV F Full 9553
Raw accumulated encoder pulses of the standard encoder, measured in ppr x 4
A13.16 Exp enc pos [cnt] R 0.00 0.00/0.00 PV F Full 9554
Raw accumulated encoder pulses of the expanded encoder, measured in ppr x 4
A13.17 Std sin enc mod [cnt] R 0.00 0.00/0.00 PV F Full 9204
Module of “A” and “B” trace of sinusoidal encoder on std port. Encoder peak voltage is
constantly monitored and the alarm Speed feedback loss is generated if it is outside the
range: min=IPA 1902/5, max=IPA 1902 * 2.
A13.18 CPU1 runtime [%] R 0.00 0.00/0.00 PV V-F-S Full 3230
Time needed by the CPU1 (microprocessor)
A13.19 CPU2 runtime [%] R 0.00 0.00/0.00 PP V-F-S Full 3240
Time needed by the CPU2 (microprocessor)
A14 DISPLAY / Drive IDs
A14.00 Drive cont curr [A] RW CALC 0.00/0.00 FK V-F-S Easy 1460
Drive maximum continuos current rating; its default value depends on the drive size and
applicable derating factors.
A14.01 Drive size N/A R D.Size 0/20 DK V-F-S Easy 114
Drive size rating in kW (ULN = 400Vac, IEC 146 Class 1) of Hp (ULN = 460Vac / 575Vac,
IEC 146 Class 2):
400/460Vac Series 575Vac Series
[0] 0.75kW-0.75Hp [2] 575V - 2.0Hp
[1] 1.5kW - 1.5Hp [3] 575V - 3.0Hp
[2] 2.2kW - 2.0Hp [4] 575V - 5.0Hp
[3] 3.0kW - 3.0Hp [5] 575V - 7.5Hp
[4] 4.0kW - 5.0Hp [6] 575V - 10Hp
[5] 5.5kW - 7.5Hp [7] 575V - 15Hp
[6] 7.5kW - 10Hp [8] 575V - 20Hp
[7] 11kW - 15Hp [9] 575V - 25Hp