MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 105
A13.05 RG sensor temp [°C] R 0.00 0.00/0.00 PV V-F-S Easy 9073
Temperature on the RV33 regulation card
A13.06 IA sensor temp [°C] R 0.00 0.00/0.00 PV V-F-S Easy 9095
Temperature of the heatsink incoming air (available for 22kW/25Hp and higher)
A13.07 Sequencer status N/A R 0 0/16 DV V-F-S Easy 9090
Sequencer status of drive State Machine. It controls the drive running and starting,
accounting for protection & alarming, command sequence, and reset status.
State Sequencer status:
1 Magnetization running
2 Magnetization completed, Stop
3 Start
4 Fast stop, Stop
5 Fast stop, Start
9 No alarm, drive is ready to accept all commands
10 Magnetization running and Start command already present
12 Alarm active
16 Alarm not active, waiting for reset
A13.08 Magn Curr ref [A] R 0.00 0.00/0.00 PV F-S Full 3130
Drive magnetizing current reference
A13.09 Trq Cur ref [A] R 0.00 0.00/0.00 PV F-S Full 3140
Drive torque current reference
A13.10 Flux ref [Wb] R 0.00 0.00/0.00 PV F-S Full 3180
Drive flux reference
A13.11 Flux [Wb] R 0.00 0.00/0.00 PV F-S Full 3190
Drive flux
A13.12 Mot OL accum % [%] R 0.00 0.00/0.00 PV V-F-S Full 1670
Motor I2t overload accumulator. When 100% is reached Mot overload alarm is generated
and output inverter current is reduced to motor continuous current .
A13.13 BU OL accum % [%] R 0.00 0.00/0.00 PV V-F-S Full 1781
Braking Unit I2t overload accumulator. When 100% is reached BU overload alarm is