Index MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 112 ARTDrive V2 series - Instruction Manual
For AVy... (230...480Vac):
[0] Standard 400V
[1] Standard 460V
For AVy...-5 (575Vac):
[0] Standard 575V
[1] Standard 575V
NOTE! By selecting one of the two options, the motor standard parameters with 400V (or
460V) are loaded making reference to the used Drive size.
Through this process, motor data is overwritten.
3kW
Motor: 3 phase
1420 rpm
Motor & Co.
Type: ABCDE
400 V
IP54
Made in ..............
6.7 A
IEC 34-1 / VDE 0530
Iso Kl F
Nr
.
12345-91
S1
50 Hz
Power factor
0.8
B0C.01
I nom
Rated voltage
Rated power
Rated speed (n )
N
2Hp
Motor: 3 phase
1750 rpm
Motor & Co.
Type: ABCDE
575 V
IP54
Made in ..............
2A
IEC 34-1 / VDE 0530
Iso Kl F
Nr
.
12345-91
S1
60 Hz
Power factor
0.83
I nom
Rated voltage
Rated power
Rated speed (n )
N
Efficiency
86.5
B0C.00
B0C.05
B0C.02 B0C.01 B0C.00
B0C.05
B0C.02
Figure B0D.07: Motor Nameplate (Example: kW rating for 400V motor and Hp rating for 575V motor)
B0E STARTUP / Drv & Mot config / Autotune
BOE.00 Complete rot Easy
Complete self -tuning of current and flux loop with a moving rotor “Press [I] key” enable
data detection command (12 drive terminal must be cycle to +24Vdc).
BOE.01 Complete still Easy
Complete self-tuning of current and flux loop with a stopped rotor “Press [I] key” enable
data detection command (12 drive terminal must be cycle to +24Vdc).
BOE.02 CurrReg Easy
Self-tuning of current loop only with stopped motor “Press [I] key”enable data detection
command (12 drive terminal must be cycle to +24Vdc).
BOE.03 FluxReg rot Full
Self-tuning of flux loop with a moving rotor only “Press [I] key” enable data detection
command (12 drive terminal must be cycle to +24Vdc).
BOE.04 FluxReg still Full
Self-tuning of flux loop with a stopped rotor only “Press [I] key” enable data detection
command (12 drive terminal must be cycle to +24Vdc).