Chapter 6 Parameter • 128 ARTDrive V2 series - Instruction Manual
C00.02 Term Stop src N/A RWS Ipa4000 PList 16 PIN V-F-S-B Full 9211
Ipa 4000 - NULL = Default
It allows to select the signal to generate the terminal strip Stop command.
ªª
ªª
ª
Pick List 16
NOTE! Signal active only when “C00.20 - Commands select = [1] TerminalEdge
The Start and Stop commands can be controlled, as an alternative, via:
• a single terminal
in this case (+24V) 1 refers to the Start and (open) 0 to the Stop
+ 24V
START=Closed, STOP=open
Figure C00.02-1: Start/Stop controlled via single terminal
• two terminals connected with buttons
in this case the change of state is caused by the positive edge (0 to1) on the
terminal.
START
STOP
+ 24V
START
STOP
+ 24V
Figure C00.02-2: Start/Stop controlled via two terminals with buttons
C00.03 Term Local src N/A RWS Ipa4000 Plist 16 PIN V-F-S-B Easy 9212
Ipa 4000 - NULL = Default
It allows to select the signal to obtain the local commands by keypad.
ªª
ªª
ª
Pick List 16
The following picture shows the selection logic for the source of Start and Stop
commands:
[1] Local
Command source
selectorC00-20
[2] Digital Level
[1] Terminal Edge
C00-43
C00-03 = Digital input
To d rive command logic
[0]Terminal Level
[0] Remote
[3] Digital Edge
[4] I O Keys
Figure C00.03: Command selection
When the selector (dedicated digital input) is 0 (Remote), Start and Stop commands
come from the source specified by parameter C00.20.
When the selector (dedicated digital input) is 1 (Local), Start and Stop commands come
from the keypad, regardless what is set into parameter C00.20.