MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 135
Input 1 signal.
ªª
ªª
ª
Pick List 3
C01.01 AI 1 alt sel src N/A RWS Ipa4000 PList 3 PIN V-F-S-B Full 5012
Ipa 4000 - NULL = Default
It connects the selected signal to the selector of the alternative reference for An. Inp. 1
block.
ªª
ªª
ª
Pick List 3
C01.10 AI 1 type N/A RWS 0 0/2 DP V-F-S-B Easy 5000
[0] -10V .. +10V Input connects a signal with a maximum voltage of +/-10V. (The change in
the motor rotation direction is obtained according to the signal polarity). Input
voltage > 10V or >-10V cause saturation of the count value.
[1] 0.20mA,0.10V On the input it’s possible to connect a max voltage of +10V or a
0…20mAcurrent signal. The signal must always have a positive sign, through
which, if used as a reference, it is possible to change the motor rotation
direction via “AI 1 sgn src”
[2] 4..20mA On the input it is possible to connect a 4… 20mA current signal. The signal
must always have a positive sign through which, if used as a reference, it is
possible to change the motor rotation direction via “AI 1 sgn src”. Through the
An inp X <thr output it is possible to state if the current signal is lower than
the one of the set threshold. If the current is <= 4mA , the output supplies a
signal (error signal). This, for example, can be combined with a digital output
NOTE! “An inp 1 type” selection requires a correct jumpers configuration of RV33
regulation card:
-10V...+10V & 0..10V S8=OFF – S9=OFF – S10=OFF
0..20mA & 4..20mA S8=ON – S9= ON – S10= ON
C01.11 AI 1 alt value [cnt] RWS 0 -32767/32767 PV V-F-S-B Full 5002
Alternative reference value in count for Analog input 1.
C01.12 AI 1 thr [%] RWS 20 -100/100 PP V-F-S-B Easy 5003
Analog Input 1 threshold value 100% is equal to 10V or 20mA.
C01.13 AI 1 scale N/A RWS 1 -16/16 PP V-F-S-B Easy 5004
Analog Input 1 scale factor.