Index
MENUMENU
MENUMENU
MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 144 ARTDrive V2 series - Instruction Manual
C06.10 AI 2X type N/A RWS 0 0/2 DP V-F-S-B Full 5080
[0] -10V .. +10V As for “ AI 1 type” parameter description above
[1] 0.20mA,0.10V As for “ AI 1 type” parameter description above
[2] 4..20mA As for “ AI 1 type” parameter description above
NOTE! “An inp 2X type” selection requires a correct jumpers configuration of “EXP..”
expansion regulation card installed.
C06.11 AI 2X thr [%] RWS 20 -100/100 PP V-F-S-B Full 5082
Analog Input 2X threshold value 100% is equal to 10V or 20mA.
C06.12 AI 2X scale N/A RWS 1 -16/16 PP V-F-S-B Full 5083
Analog Input 2X scale factor.
C06.13 AI 2X offset [%] RWS 0 -100/100 PP V-F-S-B Full 5081
Analog Input 2X offset count value 100% is equal to 10V or 20mA.
C06.14 AI 2X low lim [cnt] RWS -16384 -32768/32767 PP V-F-S-B Full 5085
Lower limit of the Analog Input 2X block output in count (see figure of Analog Input 1X).
C06.15 AI 2X hi lim [cnt] RWS 16383 -32768/32767 PP V-F-S-B Full 5086
Upper limit of the Analog Input 2X block output in count (see figure of Analog Input 1X).
C05.16 AI 2X offs tune / Start?
Autotune command for the Analog Input 2X offset. Input automatic fine-tuning.
To run the autotune, put the input signal to its minimum value and execute “Start ?”
command.
C06.17 AI 2X gain tune / Start?
Autotune command for the Analog Input 2X gain.
Conditions containing an offset can be compensated. To run the autotune, put the input
signal to its maximum value and execute “Start ?” command
C06.20 AI 2X output [cnt] R 0.00 -32768/32767 PV V-F-S-B Full 5087
Analog Input 2X output count displaying.
C06.21 AI 2X < thr N/A R 0 0/1 DV V-F-S-B Full 5088
Display of threshold compensator state of Analog Input 2X (1 = the condition is true).