MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 143
C05.13 AI 1X offset [%] RWS 0 -100/100 PP V-F-S-B Full 5061
Analog Input 1X offset count value 100% is equal to 10V or 20mA.
C05.14 AI 1X low lim [cnt] RWS -16384 -32768/32767 PP V-F-S-B Full 5065
Lower limit of the Analog Input 1X block output in count (see figure of Analog Input 1
description above)
C05.15 AI 1X hi lim [cnt] RWS 16383 -32768/32767 PP V-F-S-B Full 5066
Upper limit of the Analog Input 1X block output in count (see figure of Analog Input 1X ).
C05.16 AI 1X offs tune / Start?
Autotune command for the Analog Input 1X offset. Input automatic fine-tuning.
To run the autotune, put the input signal to its minimum value and execute “Start ?”
command.
C05.17 AI 1X gain tune / Start?
Autotune command for the Analog Input 1X gain. Conditions containing an offset can be
compensated. To run the autotune, put the input signal to its maximum value and execute
“Start ?” command
C05.20 AI 1X output [cnt] R 0.00 -32768/32767 PV V-F-S-B Full 5067
Analog Input 1X output count displaying
C05.21 AI 1X < thr N/A R 0 0/1 DV V-F-S-B Full 5068
Display of threshold compensator state of Analog Input 1X (1 = the condition is true)
C05.23 AI 1X gain N/A RWS 1 -16/16 PP V-F-S-B Full 5064
Analog Input 1X gain count value displaying
C06 INTERFACE / An Inp 2X
See Analog Input 1X diagram and description details above.
C06.00 AI 2X sgn src N/A RWS Ipa4000 PList 3 PIN V-F-S-B Full 5089
Ipa 4000 - NULL = Default
It connects the selected signal to the selector of the multiplier input: if the signal is 0,
multiply by +1, or if the signal is 1, multiply by -1. The multiplier allows to invert Analog
Input 2X signal.
ªª
ªª
ª
Pick List 3