Chapter 6 Parameter • 142 ARTDrive V2 series - Instruction Manual
C05 INTERFACE / An Inp 1X
This Block refers to possible Option Expansion cards. See the considerations listed in the
previous paragraph, including the parameter description.
The points of difference are:
• No input filter is present
• No alternative reference can be selected (the “AI 1X alt sel src” is missing)
• The Block has a sampling time of 8 msec
AI 1x sgn src
*-1
*+1
X
AI 1x type
AI 1x lo lim
AI 1x hi lim
AI 1x scale
AI 1x thr
+
+
AI 1x < thr
AI 1x output
AI 1x offset
Terminal Input
Figure C05: Expanded analog input block
C05.00 AI 1X sgn src N/A RWS Ipa4000 PList 3 PIN V-F-S-B Full 5069
Ipa 4000 - NULL = Default
It connects the selected signal to the selector of the multiplier input: if the signal is 0,
multiply by +1, or if the signal is 1, multiply by -1. The multiplier allows to invert Analog
Input 1X signal.
ªª
ªª
ª
Pick List 3
C05.10 AI 1X type N/A RWS 0 0/2 DP V-F-S-B Full 5060
[0] -10V .. +10V As for “ AI 1 type” parameter description above
[1] 0.20mA,0.10V As for “ AI 1 type” parameter description above
[2] 4..20mA As for “ AI 1 type” parameter description above
NOTE! “An inp 1X type” selection requires a correct jumpers configuration of “EXP..”
expansion regulation card installed.
C05.11 AI 1X thr [%] RWS 20 -100/100 PP V-F-S-B Full 5062
Analog Input 1X threshold value 100% is equal to 10V or 20mA.
C05.12 AI 1X scale N/A RWS 1 -16/16 PP V-F-S-B Full 5063
Analog Input 1X scale factor.