Index
MENUMENU
MENUMENU
MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 146 ARTDrive V2 series - Instruction Manual
INTERFACE / Analog Outputs
Drive has 2 standard voltage outputs and 4 expanded analog outputs (1x and 2x = voltage
outputs, 3x and 4x=current outputs).
The Blocks of the analog outputs allow to turn an internal signal into a voltage signal (or a
current signal if the EXP-D20A6 option card is used) available on the terminal strip.
.
.
.
.
Analog Output 1
AO 1 scale
1
AO1hilim
16383 cnt
AO1lolim
-16384 cnt
AO1src
NULL
AO 1 inp AO 1 mon
CALIBRATION TO +/-10 V OUTPUT
An out 1 mon (in counts) * An out 1 scale = An out 1 hi lim (in counts) = 10 V
An out 1 mon (in counts) * An out 1 scale = An out 1 lo lim (in counts) = -10 V
Figure C08: Analog outputs block
C08 INTERFACE / An Out 1
C08.00 AO 1 src N/A RWS Ipa4000 PList 2 PIN V-F-S-B Easy 3570
Ipa 4000 - NULL = Default
It allows to connect the selected signal to the Analog output 1. Refer to signals List 2 of
Pick List section.
C08.10 AO 1 scale N/A RWS 1 -10 1/0 PP V-F-S-B Easy 6012
Scale or multiplicative factor of Analog output 1.
C08.11 AO 1 hi lim [cnt] RWS 16383 0/32767 PP V-F-S-B Full 6010
Analog output 1 count value aimed at obtaining +10V. Value must be higher than zero.
C08.13 AO 1 low lim [cnt] RWS -16384 -32768/0 PP V-F-S-B Full 6011
Analog output 1 count value aimed at obtaining -10V. Value must be higher than zero.
C08.20 AO 1 inp [cnt] R 0 -32768/32767 PP V-F-S-B Easy 6013
Analog output 1 count value displaying.
C08.21 AO 1 mon [%] R 0 -100/100 PP V-F-S-B Easy 6014
Analog output 1 value displaying 100% is equal to 10V.