ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 147
C09 INTERFACE / An Out 2
See Analog Otuput 1 diagram and description details above.
C09.00 AO 2 src N/A RWS Ipa4000 PList 2 PIN V-F-S-B Easy 3580
Ipa 4000 - NULL = Default
It allows to connect the selected signal to the Analog output 2.
ªª
ªª
ª
Pick List 2
C09.10 AO 2 scale N/A RWS 1 -10 1/0 PP V-F-S-B Easy 6017
Scale or multiplicative factor of Analog output 1.
C09.11 AO 2 high lim [cnt] RWS 16383 0/32767 PP V-F-S-B Full 6015
Analog output 2 count value aimed at obtaining +10V. Value must be higher than zero
C09.12 AO 2 low lim [cnt] RWS -16384 -32768/0 PP V-F-S-B Full 6016
Analog output 2 count value aimed at obtaining -10V. Value must be higher than zero
C09.20 AO 2 inp [cnt] R 0 -32768/32767 PP V-F-S-B Easy 6018
Analog output 2 count value displaying.
C09.21 AO 2 mon [%] R 0 -100/100 PP V-F-S-B Easy 6019
Analog output 2 value displaying 100% is equal to 10V.
C10.00
C10.00 Exp AO Enable N/A RWS 0 0/1 DV V-F-S-B Full 3901
It enables the expanded analog outputs:
[0] Disabled
[1] Enabled
C11 INTERFACE / An Out 1X
See Analog Output 1 diagram and description details above.
C11.00 AO 1X src N/A RWS Ipa4000 PList 2 PIN V-F-S-B Full 4090
Ipa 4000 - NULL = Default
It allows to connect the selected signal to the Analog output 1X.
ªª
ªª
ª
Pick List 2