Index
MENUMENU
MENUMENU
MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 199
E06.02 Dig SE flx level [%] RWS 100 10/100 PV V Easy 3536
Digital value of V/f Save Energy Flux.
E06.03 SE flx ramp time [sec] RWS 10 0/100 PP V Easy 3537
V/f Save Energy Flux Level ramp time value
E07 REG PARAM / VFAutCapt
The function allows the Drive to catch an already rotating motor, “Autocapture”.
An automatic restart of the drive is possible after a “Retrying” temporary alarm condition.
Through the E07.00 - V/f catch cmd source it is possible to select the origin of the
command signal enabling the function. In the configurations the function can be
parameterized according to the application.
E07.00 V/f catch cmd N/A RWS Ipa4000 PList3 PIN V Easy 3582
Ipa 4000 - NULL = Default
It select the origin of the signal of V/f Auto Capture command.
ªª
ªª
ª
Pick List 3
E07.01 Spd search time [sec] RWS 10 0.05/20 PP V Easy 3545
It states the change of the Drive output frequency. It shows the time needed to perform a
frequency change from zero to the motor rated one if the output current is equal to the
motor rated one.
E07.02 Vlt search time [sec] RWS 1 0.01/20 PP V Easy 3550
It states the machine flux change. It shows the time needed to perform a flux change
from zero to the motor rated one, if the output current is equal to the motor rated one.
E07.03 Catch init spd [rpm] RWS Calc 0.00/- PP V Easy 3555
It states the starting speed for the synchronism search.
E07.04 Catch demag dly [sec] RWS 3 0/10 PP V Easy 3560
Delay time for the motor demagnetization before performing the synchronism search (in
case the “Autocapture” function is present).
E07.05 Catch retry dly [sec] RWS 3 0/10 PP V Easy 3565
Delay time for the motor demagnetization (with the “Retrying” function).