MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 215
F03.01 Spd 0 enable N/A RWS 0 0/1 DP F-S-B Full 3720
Apart from gain adaptive function, it is possible to have another set of gains when speed
reference is below Speed 0 reference threshold parameter. Function must be enabled by
this parameter:
[0] Disable
[1] Enable
F03.10 Dig spd 0 ref [cnt] RWS 0.00 0.00/0.00 PV V-F-S-B Full 3721
Digital speed zero reference value, selectable through Pick List 20 of F03.00 - Spd 0 ref src.
ªª
ªª
ª
Pick List 20
F03.11 Spd 0 P gain % [%] RWS Calc 0/100 PP F-S-B Full 3722
Proportional speed 0 regulator gain at zero speed.
F03.12 Spd 0 I gain % [%] RWS Calc 0/100 PP F-S-B Full 3723
Integral speed 0 regulator gain at zero speed.
F03.13 Spd 0 speed thr [rpm] RWS 30 0/.. PP V-F-S-B Full 3724
Speed 0 speed threshold value.
F03.14 Spd 0 spd delay [msec] RWS 500 0/30000 PP V-F-S-B Full 3725
Speed 0 speed delay value.
F03.15 Spd 0 ref thr [rmp] RWS 30 0/.. PP V-F-S-B Full 3726
Speed 0 reference threshold value.
F03.16 Spd 0 ref delay [msec] RWS 100 0/30000 PP V-F-S-B Full 3727
Speed 0 reference delay value.
F03.17 Spd = zero N/A R 0 0/1 DV V-F-S-B Full 3728
Speed zero state displaying:
0 = speed ≠ 0
1 = speed = 0
F03.18 Ref = zero N/A R 0 0/1 DV V-F-S-B Full 3729
Reference zero state displaying:
0 = Reference ≠ 0
1 = Reference = 0.