ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 231
TORQUE / Torque limit
After Torque control, the Torque Current Limit can modify Torque current reference.
Through the G01.00 - Tcurr lim sel parameter it is possible to select, into a list, the limit
to be controlled:
• OFF None
• T lim +/- Positive or negative limit
• T lim mot/gen Generator motor limit
• T lim gen Power limit on the generated power (selection not available in V/f control reg.
mode)
• T lim Vdc ctrl Limit on the DC link voltage control (selection not available in V/f control reg.
mode)
Furthermore, via the G01.01 - Tcurr lim + and G01.02 - Tcurr lim - parameters it is
possible to set the positive and negative current limit value.
G01 TORQUE / Trq limit
G01.00 Tcurr lim sel N/A RWS 0 0/4 DV V-F-S-B Easy 1190
[0] Off
[1] Tlim +/-
[2] Tlim mot/gen
[3] Tlim gen pwr
[4] Tlim Vdc ctrl
NOTE! Selection “3” and “4” are not available in V/f control regulation mode.
G01.01 Tcurr lim + [A] RWS Calc 0.00/Calc PV V-F-S-B Easy 1210
Positive Torque current limit motor value.
G01.02 Tcurr lim - [A] RWS Calc 0.00/Calc PV V-F-S-B Easy 1220
Negative Torque current limit generator value.
G01.03 Max regen power [kW] RWS Calc 0.00/Calc PV F-S-B Easy 1310
Maximum regenerating power limit value.
G01.04 Inuse Tcurr L+ [A] R 0.00 0.00/- PV V-F-S-B Full 1250
In use value of positive Torque current limit.
G01.05 Inuse Tcurr L- [A] R 0.00 0.00/- PV V-F-S-B Full 1260
In use value of negative Torque current limit.