TORQUE / Voltage DC Control Regulator
NOTE! Menu accessible with Access Level = FULL
The function is available only with a Sensorless and Field Oriented regulation mode.
It allows the control:
• of the DC link voltage during regenerating (ex. deceleration), to avoid the
Overvoltage alarm trip
or
• the control of the power recovered on the DC link during regenerating
The two functions are activated by setting the following parameters respectively in
the G01.00 - Tcur lim sel of the Torque Setpoint:
• [3] T lim gen pwr For a control of the recovered power
• [4] T lim Vdc ctrl For a control of the DC link voltage
During such phases the G02.00 - VdcCtrl P gain and G02.01 - VdcCtrl I gain
parameters (gains) allow the tuning, if required, of the DC link control.
G02 TORQUE / VdcCtrReg
G02.00 VdcCtrl P gain [A/V] RWS Calc 0/Calc PP F-S-B Full 2295
Proportional gain of Voltage DC Control Regulator.
G02.01 VdcCtrl I gain [A/V/s] RWS Calc 0/Calc PP F-S-B Full 2296
Integral gain of Voltage DC Control Regulator.