ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 233
TORQUE / Voltage DC Control Regulator
NOTE! Menu accessible with Access Level = FULL
The function is available only with a Sensorless and Field Oriented regulation mode.
It allows the control:
of the DC link voltage during regenerating (ex. deceleration), to avoid the
Overvoltage alarm trip
or
the control of the power recovered on the DC link during regenerating
The two functions are activated by setting the following parameters respectively in
the G01.00 - Tcur lim sel of the Torque Setpoint:
[3] T lim gen pwr For a control of the recovered power
[4] T lim Vdc ctrl For a control of the DC link voltage
During such phases the G02.00 - VdcCtrl P gain and G02.01 - VdcCtrl I gain
parameters (gains) allow the tuning, if required, of the DC link control.
G02 TORQUE / VdcCtrReg
G02.00 VdcCtrl P gain [A/V] RWS Calc 0/Calc PP F-S-B Full 2295
Proportional gain of Voltage DC Control Regulator.
G02.01 VdcCtrl I gain [A/V/s] RWS Calc 0/Calc PP F-S-B Full 2296
Integral gain of Voltage DC Control Regulator.