MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 252 ARTDrive V2 series - Instruction Manual
L00 ALARM CFG / Fault reset
L00.00 Fault reset src N/A RWS Ipa4000 PList 41 PIN V-F-S-B Easy 9076
Ipa 4000 - NULL = Default
It allows to select the Fault reset command signal .
ªª
ªª
ª
Pick List 41
L01 ALARM CFG / UV cfg
It trips when the voltage on the drive DC link is lower than the minimum threshold
according to the Mains voltage setting.
L01.00 UV restart N/A RWS 1 0/1 DP V-F-S-B Easy 9050
Undervoltage restart:
[0] off
[1] on
L01.01 UV restart time [ms] RWS 1000 0/30000 PP V-F-S-B Easy 9051
Undervoltage restart time
L02 ALARM CFG / OV cfg
It trips when the voltage on the drive DC link is higher than the maximum threshold
according to the Mains voltage setting.
L02.00 OV restart N/A RWS 0 0/1 DP V-F-S-B Easy 9052
Overvoltage restart:
[0] off
[1] on
L02.01 OV restart time [ms] RWS 1000 0/30000 PP V-F-S-B Easy 9053
Overvoltage restart time
L03 ALARM CFG / IGBT des
NOTE! Menu accessible with Access Level = FULL.
It trips when the IGBT instantaneous overcurrent is detected by gate desaturation sensing
circuit.
L03.00 DS restart N/A RWS 0 0/1 DP V-F-S-B Full 9046
IGBT desaturation restart:
[0] off
[1] on