MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 253
L03.01 DS restart time [ms] RWS 1000 0/30000 PP V-F-S-B Full 9047
IGBT desaturation restart time.
L04 ALARM CFG / Inst IOC
It trips when the IGBT instantaneous overcurrent is detected by output current sensor.
L04.00 IOC restart N/A RWS 0 0/1 DP V-F-S-B Easy 9063
Instantaneous overcurrent restart:
[0] off
[1] on
L04.01 IOC restart time [ms] RWS 1000 0/30000 PP V-F-S-B Easy 9064
Instantaneous overcurrent restart time.
L05 ALARM CFG / Ground
It trips when the output phase discharge to ground: Ground fault
L05.00 GF activity N/A RWS 2 1/6 DP V-F-S-B Easy 9640
Ground fault activity:
[1] Ignore
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L05.01 GF threshold [A] RWS D.Size Calc/D.Size PP V-F-S-B Easy 9641
Ground fault threshold
L06 ALARM CFG / EF cfg
It trips when the External fault input is active.
L06.00 EF src N/A RWS Ipa4000 PList 3 PIN V-F-S-B Easy 9075
Ipa 4000 NULL = Default
It allows to connect the External fault input terminal strip.