EasyManua.ls Logo

GEFRAN-SIEI ARTDrive Vector V2 Series - Page 254

GEFRAN-SIEI ARTDrive Vector V2 Series
387 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Index
MENUMENU
MENUMENU
MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 254 ARTDrive V2 series - Instruction Manual
L06.01 EF activity N/A RWS 3 2/6 DP V-F-S-B Easy 9060
External fault activity:
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L06.02 EF restart N/A RWS 0 0/1 DP V-F-S-B Easy 9061
External fault restart:
[0] off
[1] on
L06.03 EF restart time [ms] RWS 1000 0/30000 PP V-F-S-B Easy 9062
External fault restart time
L06.04 EF hold off [ms] RWS 0 0/30000 PP V-F-S-B Easy 9600
External fault hold off
L07 ALARM CFG / Motor OT
Motor Over-Temperature indicated via thermal contact or PTC thermistor on 78-79 drive
regulation board terminals.
L07.00 MOT activity N/A RWS 2 2/6 DP V-F-S-B Easy 9065
Motor Over-Temperature activity:
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L07.01 MOT restart N/A RWS 0 0/1 DP V-F-S-B Easy 9066
Motor Over-Temperature restart:
[0] off
[1] on
L07.02 MOT restart time [ms] RWS 1000 0/30000 PP V-F-S-B Easy 9067
Motor Over-Temperature restart time

Table of Contents