Index
MENUMENU
MENUMENU
MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 257
L11.00 ISB activity N/A RWS 3 2/6 DP V-F-S-B Full 9068
ISBus Fault alarm activity:
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L11.01 ISB restart N/A RWS 0 0/1 DP V-F-S-B Full 9069
ISBus Fault alarm restart:
[0] off
[1] on
L11.02 ISB restart time [ms] RWS 1000 0/30000 PP V-F-S-B Full 9070
ISBus Fault alarm restart time
L12 ALARM CFG / Comm F
It trips when LAN communication is interrupted (LAN communication between drive and
Field Bus optional card)
L12.00 CCF activity N/A RWS 3 2/6 DP V-F-S-B Easy 9074
Comm card fault activity:
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L12.01 CCF restart N/A RWS 0 0/1 DP V-F-S-B Easy 4200
Comm card fault restart:
[0] off
[1] on
L12.02 CCF restart time [ms] RWS 1000 0/30000 PP V-F-S-B Easy 4201
Comm card fault restart time
L13 ALARM CFG / APC F
It trips when optional coprocessor communication is interrupted (coprocessor
communication between drive and APC 100 optional card).