MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 256 ARTDrive V2 series - Instruction Manual
L09.01 RGS restart N/A RWS 0 0/1 DP V-F-S-B Easy 9058
Regulation card Sensor Over-Temperature restart:
[0] off
[1] on
L09.02 RGS restart time [ms] RWS 1000 0/30000 PP V-F-S-B Easy 9059
Regulation card Sensor Over-Temperature restart time
L09.03 RGS hold off [ms] RWS 10000 0/30000 PP V-F-S-B Easy 9605
Regulation card Sensor Over-Temperature hold off
L10 ALARM CFG / Intake OT
Intake air Sensor Over-Temperature (only for model AVy 4220 and over)
L10.00 IAS activity N/A RWS 3 2/6 DP V-F-S-B Easy 9087
Intake air Sensor Over-Temperature activity:
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L10.01 IAS restart N/A RWS 0 0/1 DP V-F-S-B Easy 9088
Intake air Sensor Over-Temperature restart:
[0] off
[1] on
L10.02 IAS restart time [ms] RWS 1000 0/30000 PP V-F-S-B Easy 9089
Intake air Sensor Over-Temperature restart time
L10.03 IAS hold off [ms] RWS 10000 0/30000 PP V-F-S-B Easy 9606
Intake air Sensor Over-Temperature hold off
L11 ALARM CFG / ISBus F
NOTE! Menu accessible with Access Level = FULL
It trips when LAN communication is interrupted: ISBus Fault (LAN communication
between drive and ISBus optional card)