ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 271
COMM / ISBus
Configuration for the data exchange with the ISBus card. As for the process channel
programming see the description of the Field Bus communication.
The interface is made of 8 writing Words plus 8 reading Words.
NOTE! The ISBus card cannot be used with a APC100 option card since they both occupy
the same card mounting space.
The menu contains all the items needed to configure and monitor the drive parameter
assignment; the used style is the same as that of the Serial Bus Interface Menu.
In addition, the system provides some ISBus specific items.
M04 COMM / ISBus
NOTE! Menu accessible with Access Level = FULL.
M04.00 ISBus enable N/A RWS 0 0/1 DK V-F-S-B Full 4225
It allows to enable ISBus option cards:
[0] Disabled
[1] Enabled
This parameter must be set to Enabled in order to let the drive ISBus interface work ; the
parameter configuration has to be saved and the drive has to be switched off and on
again to allow this parameter to take effect.
M04.01 ISBus Node ID N/A RWS 1 1/31 DK V-F-S-B Full 4226
Here the node address has to be entered.
M04.02 Heartbeat time [ms] RWS 0.00 0.00/10000 PP V-F-S-B Full 4241
Through this parameter it is possible to set the Heartbeat alarm timeout which will cause
an alarm condition.
M04.03 ISB Card status N/A R 0 0/7 DP V-F-S-B Full 4227
It is read-only and reports the ISbus current state; to this purpose, the ST register is read.
The states to be displayed as alphanumeric string are:
Reset
Off line
Standby
On Line
M04.04 Last ISB error N/A R 0 0/0xffff DP V-F-S-B Full 4228
It is a read-only parameter showing the cause of the last ISBus alarm intervention; the
value is reported as an alphanumeric string:
No error There hasn’t been any alarm