MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 308 ARTDrive V2 series - Instruction Manual
P01.02 Cmp 2 inp 2 src N/A RWS Ipa6058 PList 5 PIN V-F-S-B Full 6066
Ipa 6058 - Cmp 2 inp 2 = Default
It allows to select the origin of the input signal 2 to be compared of the Compare 2 block.
ªª
ªª
ª
Pick List 5
P01.10 Cmp 2 inp 0 N/A RWS 0.00 - - PV V-F-S-B Full 6056
Value of the internal input signal 0, default connected to Cmp 2 inp 0 src
P01.11 Cmp 2 inp 1 N/A RWS 0.00 - - PV V-F-S-B Full 6057
Value of the internal input signal 1, default connected to Cmp 2 inp 1 src
P01.12 Cmp 2 inp 2 N/A RWS 0.00 - - PV V-F-S-B Full 6058
Value of the internal input signal 2, default connected to Cmp 2 inp 2 src
P01.20 Cmp 2 function N/A RWS 0 0/10 DP V-F-S-B Full 6059
[0] None
[1] I0 == I1
[2] I0 != I1
[3] I0 < I1
[4] I0 > I1
[5] I0 < I1 < I2
[6] |I0| == |I1|
[7] |I0| != |I1|
[8] |I0| < |I1|
[9] |I0| > |I1|
[10] |I0|< |I1| <|I2|
P01.21 Cmp 2 window [cnt] RWS 0.00 0.00/- PP V-F-S-B Full 6060
It allows to set a window stating an acceptable range among the signals of the Compare
2 block.
P01.22 Cmp 2 delay [sec] RWS 0.00 0.00/30 PP V-F-S-B Full 6061
It allows to set a delay in seconds on the comparison transition in the Compare 2 block
P01.23 Cmp 2 inversion N/A RWS 0 0/1 DP V-F-S-B Full 6062
It allows to invert the Compare 2 block output signal:
[0] Not inverted
[1] Inverted