ARTDrive V2 series - Instruction Manual Chapter 4 Wiring Procedure • 55
Figure 4.5.1.2: Example for Relay Interface
AC Input Contactor
K1M
ENABLE
K1MX
DriveOK
START
K2
FAST STOP
DriveOK
Reset
115 VAC from CPT
fedfrom AC incoming
START
PB
START
K2
STOP
PB
80
82
FAST STOP
K0
Drive Healthy
picks up if OK
SNF
P. B .
latchedonpush, pull to reset
after the process hasstopped
H
N
Coil Suppressor
EXTERNAL
ESTOPS
EXTERNAL
RUN
PERMISSIVES
SNF
System Not Fault
SNF
- Time after deenergization -
Setgreater than the maximum
decel ramp
An AC Input contactor is usually not required.
Opening the AC Input contactor will cause the
ARTDriveAtolose control power
19
14
+ 24V
FAST STOP
KO
19
13
+ 24V
START
K2
19
12
+ 24V
ENABLE
K1M
(Digital input 2)
(Digital input 1)
(Digital input 0)
NOTE! 1 - ENABLE must remain energized during a normal STOP or FAST STOP for
the ARTDrive to decel on a ramp.
ENABLE may be de energized after zero speed is achieved.
2 - ENABLE must be de energized to power up and to reset a fault or alarm.
3 - FAST STOP command is necessary to set:
C00.06 - Fast Stop src = DI 2 mon.
4 - STOP command is necessary to set:
C00.00 - Term Str Stp src = DI 1 mon.
5 - Opening the input will cause labeled drive reaction.