Model 574 Programmable Counting System (PCS)
262 - GSE Scale Systems
Selection Coarse Zero
0%e 0%
1%e 25%
2%e 50%
3%e 75%
4%e 100%
5%e 125%
6%e 150%
7%e 175%
8%e 0%
9%e -25%
10%e -50%
11%e -75%
12%e -100%
13%e -125%
14%e -150%
15%e -175%
P61105.Fine Zero
This parameter shows a number ranging approximately
between +/- 8,000,000. This number is calculated during
the calibration mode. Every 2,000,000 increments
corresponds to 25% of the full range.
P61106.CGain
This value is established by the indicator during the
calibration mode. The 4 values are 25, 50, 100 and 200.
If transfering to another 574 from an ASCII file, modify
the file with one of the following selections.
Selection Coarse Gain
0%e 25
1%e 50
2%e 100
3%e 200
P61107.Fine Gain
This parameter shows the fine calibration factor
established as of the last calibration routine, ranging from
0.4 to 1.5 and normally near 1. The absolute maximum
range is 0 - 2.0. If Multi-Point Linearization is enabled
(P119) then Not Used will appear. Refer to P61110-
P61119 for more multi-point linearization information.
P61110 thru P61121 are established at the factory
(GSE) for each individual 574. If the unit’s A/D is
changed, the procedure in the Trouble Shooting and
Service chapter must be followed (Swapping the A/D
Converter).
P61110.Zero Adj25
This is a number between +/-2,000,000. Adjusts
variations in the coarse zero adjustments.
P61111.Zero Adj50
This is a number between +/-2,000,000. Adjusts
variations in the coarse zero adjustments.
P61112.Zero Ad100
This is a number between +/-2,000,000. Adjusts
variations in the coarse zero adjustments.
P61113.Gain Adj1
This number is established to compensate for variations
in adjustments in the coarse gain values established in the
preceeding parameters. The normal range is 0.94 to 0.98.
P61114.Gain Adj2
This number is established to compensate for variations
in adjustments in the coarse gain values established in the
preceeding parameters. The normal range is 0.94 to 0.98.
P61115.Gain Adj4
This number is established to compensate for variations
in adjustments in the coarse gain values established in the
preceeding parameters. The normal range is 0.94 to 0.98.
P61116.Gain Adj8
This number is established to compensate for variations
in adjustments in the coarse gain values established in the
preceeding parameters. The normal range is 0.94 to 0.98.
P61117.AIN1 NROff
Compensates zero offsets in A/D for all four gain factors
during the calibration procedure.
P61118.AIN2 NROff
Compensates zero offsets in A/D for all four gain factors
during the calibration procedure.
P61119.AIN4 NROff
Compensates zero offsets in A/D for all four gain factors
during the calibration procedure.